Our products are designed to suit specific requirements of customers
Our plants / machines are with minimum and easy maintenance.
Low operating costs due to adaptation of latest technology.
Our main aim is total customer satisfaction..
High-Vacuum Transformer Oil Filtration and Dehydration Plants
Trickle Impregnation Technique
Batch Type Trickle Impregnating Machine
Index Type Trickle Impregnating Machine
SR. NO. |
UNITS |
PARAMETERS |
BEFORE FILTRATION |
AFTER FILTRATION |
1 |
Break Down Voltage with 2.5mm Electrode Gap. |
kV |
25 |
>50- 70 |
2 |
Moisture Removal |
ppm |
50-100 |
Up to < 5 - 10 |
3 |
Neutralization Value (With IRC Option Only) |
mg of KOH/g |
0.5 |
< 0.1 |
4 |
Particle size (Filter Fineness) |
Micron |
Visible |
< 1 |
5 |
Gas Content |
% Vol./Vol. |
<10% |
< 0.1% |
It will consist of following components:
FOR FIRST STAGE OF DEGASSING:
VACUUM PUMP: Rotary Oil Sealed Pump with following specifications:
Free air displacement -*** LPM.
Make - M/s Indo-Woo sung or similar
Electric Motor – ** H.P. Foot Mounted,
Working Vacuum - < 5 torr, Ultimate vacuum - < 0.005 torr
FOR SECOND STAGE OF DEGASSING (ONLY FOR 2V PLANTS):
ROOTS PUMP: FREE AIR DISPLACEMENT: *** M³/Hr
Make – M/s Everest or similar
Electric Motor – ** H.P. Flange Mounted
VACUUM PUMP: Rotary Oil Sealed Pump with following specifications:
Free air displacement - *** LPM.
Make - M/s Indo-Woo sung or similar
Electric Motor – ** H.P. Foot Mounted,
Working Vacuum - <0.1 torr, Ultimate vacuum - 0.001torr
It will be suitable for working vacuum of either 5 – 10 torr or 0.1 – 0.5 torr. It will be provided with Rotary Oil Sealed Pump or Roots Rotary combination along with Moisture Traps (water cooled) with drain, airing valve, NRV, Vacuum Gauge will be provided as per the schematic diagram.
|
![]() |
|
![]() |
|
1V |
2V |
SINGLE STAGE DEGASSING |
DOUBLE STAGE DEGASSING |
![]() |
![]() |
Working vacuum less than 5 torr |
Working vacuum less than 0.5 torr |
X |
FLOW RATE |
![]() |
Indicates flow rate = 10 X |
T-EM-2V-600 Model
means
Plant is for transformern
oil filtration (T)
nclosed in CRCA
canopy (E), mounted on<
trailer (M) with 2-stage
degassing system(2V)
having flow-rate = 6000 LPH (600 x 10) |
OPEN STATIONERY MODEL- Suitable for indoor fixed place operation.
ENCLOSED STATIONERY MODEL – Suitable for permanent mounting on vehicle.
OPEN PORTABLE MODEL – Suitable for indoor movable operation. Small plants are suitable for carrying in the vehicle for on-site operation.
Technical Details for Two Stage Degassing Plants (Model - 1V) |
||||||||||
WORKING VACUUM: < 2 Torr; ULIMATE VACUUM: 0.005 Torr |
||||||||||
FLOW RATE | LPH |
300 |
600 |
1200 |
1800 |
2400 |
3000 |
4500 |
6000 |
|
MOTOR POWER | INLET | HP |
0.25 |
0.5 |
0.5 |
1 |
1 |
1.5 |
2 |
5 |
OUTLET | HP |
0.5 |
0.5 |
1 |
1 |
1 |
3 |
5 |
5 |
|
VACUUM -1 | HP |
0.5 |
0.5 |
1 |
1 |
1 |
2 |
2 |
5 |
|
VACUUM-2 | HP |
- |
- |
- |
- |
- |
- |
- |
- |
|
BOOSTER | HP |
- |
- |
- |
- |
- |
- |
- |
- |
|
HEATER POWER | HEATER-1 | TOTAL kW |
3 |
6 |
18 |
18 |
18 |
18 |
36 |
24 |
NOS x kW |
1 x 3 |
2 x 3 |
6 x 3 |
6 x 3 |
6 x 3 |
6 x 3 |
9 x 4 |
6 X 4 |
||
HEATER-2 | TOTAL kW |
- |
- |
- |
18 |
27 |
27 |
36 |
24 |
|
NOS x kW |
- |
- |
- |
6 x 3 |
9 x 3 |
9 x 3 |
9 x 4 |
6 X 4 |
||
HEATER-3 | TOTAL kW |
- |
- |
- |
- |
- |
- |
- |
36 |
|
NOS x kW |
- |
- |
- |
- |
- |
- |
- |
9 X 4 |
||
TOTAL (kW) | 3 |
6 |
18 |
36 |
45 |
45 |
72 |
84 |
||
VACUUM PUMP DISPLACEMENT | VACUUM-1 | M3/HR |
6 |
10.8 |
18 |
36 |
36 |
60 |
60 |
90 |
VACUUM-2 | M3/HR |
- |
- |
- |
- |
- |
- |
- |
- |
|
BOOSTER | M3/HR |
- |
- |
- |
- |
- |
- |
- |
- |
|
FILTER ELEMENTS (1 µm) | Ø63 X 500L |
0.5 |
1 |
2 |
3 |
4 |
4 |
7 |
10 |
|
SUITABLE FOR TRANSFORMERS UPTO | 750kVA |
1 MVA |
5 MVA |
15 MVA |
25 MVA |
50 MVA |
75 MVA |
100 MVA |
||
Technical Details for Two Stage Degassing Plants (Model - 2V) |
||||||||
WORKING VACUUM: < 0.3 Torr; ULIMATE VACUUM: 0.001 Torr |
||||||||
FLOW RATE | LPH |
3000 |
4500 |
6000 |
8000 |
10000 |
12000 |
|
MOTOR POWER | INLET |
HP |
1.5 |
2 |
5 |
7.5 |
10 |
10 |
OUTLET |
HP |
3 |
5 |
5 |
7.5 |
12.5 |
12.5 |
|
VACUUM -1 |
HP |
1 |
1 |
2 |
5 |
7.5 |
7.5 |
|
VACUUM-2 |
HP |
1 |
2 |
5 |
7.5 |
7.5 |
7.5 |
|
BOOSTER |
HP |
1 |
2 |
2 |
5 |
5 |
5 |
|
HEATER POWER | HEATER-1 |
TOTAL kW |
27 |
36 |
36 |
36 |
36 |
36 |
NOS x kW |
9 X 3 |
9 X 4 |
9 X 4 |
9 X 4 |
9 X 4 |
9 X 4 |
||
HEATER-2 |
TOTAL kW |
27 |
36 |
36 |
36 |
36 |
36 |
|
NOS x kW |
9 X 3 |
9 X 4 |
9 X 4 |
9 X 4 |
9 X 4 |
9 X 4 |
||
HEATER-3 |
TOTAL kW |
- |
- |
36 |
36 |
36 |
36 |
|
NOS x kW |
- |
- |
9 X 4 |
9 X 4 |
9 X 4 |
9 X 4 |
||
HEATER-4 |
TOTAL kW |
- |
- |
- |
24 |
24 |
36 |
|
NOS x kW |
- |
- |
- |
6 X 4 |
6 X 4 |
9 X 4 |
||
TOTAL (kW) |
54 |
72 |
108 |
132 |
132 |
144 |
||
VACUUM PUMP DISPLACEMENT | VACUUM-1 |
M3/HR |
18 |
36 |
60 |
90 |
120 |
120 |
VACUUM-2 |
M3/HR |
36 |
60 |
90 |
120 |
120 |
120 |
|
BOOSTER |
M3/HR |
150 |
375 |
500 |
1000 |
1000 |
1000 |
|
FILTER ELEMENTS (1 µm) | Ø63 X 500L |
4 |
7 |
10 |
12 |
16 |
18 |
|
SUITABLE FOR TRANSFORMERS UPTO | 75 MVA |
150 MVA |
250 MVA |
350 MVA |
400 MVA |
500 MVA |
||
L - 77, Additional M.I.D.C.,
Satara - 415004, (India)
Tel. No. : +91 - 2162 - 240384, 240385
Mobile :+91 - 98223 93556, 94226 05890
oilfiltrationplants.comoilfiltermachineindia.com
Designed By 360 SME Solutions